13.9.2
Functionality
Elapsed Time Integrator (TEIGGIO) function is a function that accumulates the
elapsed time when a given binary signal has been high.
The main features of TEIGGIO are
•
Applicable to long time integration (≤999 999.9 seconds).
•
Supervision of limit transgression conditions and overflow.
•
Possibility defining a warning or alarm with the resolution of 10 milliseconds.
•
Retain the integration value at a warning/alarm/overflow.
•
Possibilities for blocking and reset.
•
Report the integrated time
13.9.3
Function block
TEIGGIO
BLOCK
IN
RESET
WARNING
ALARM
OVERFLOW
ACCTIME
IEC13000005-1-en.vsd
IEC13000005 V1 EN
Figure 233:
TEIGGIO function block
13.9.4
Signals
Table 341:
TEIGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the integration and block the other outputs
IN
BOOLEAN
0
The input signal that is used to measure the
elapsed time, when its value is high
RESET
BOOLEAN
0
Reset the integration time
Table 342:
TEIGGIO Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the
warning limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the
alarm limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the
overflow limit
ACCTIME
REAL
Integrated elapsed time in seconds
Section 13
1MRK 502 048-UEN A
Logic
466
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...