The accuracy of the impedance reach is ±2% of the base
impedance; that is considered while evaluating the test results.
For the test as motor the frequency current may have 50.5 Hz in the
quadrant 1 and 2 of the R-X plane and 49.5 Hz in the quadrant 3
and 4.
Verifying the settings by secondary injection
GUID-1752CE04-7C0F-4D37-9602-B22D8096DD2D v1
It is advised to connect the analog output channels of the function block
OOSPPAM to the internal disturbance recorder (and in particular to the function
block A4RADR) in order to perform a better analysis of the tests.
If the device is in test mode, the recording of the disturbances are enabled by the
setting in
Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DisturbanceReport/DRPRDRE:1:
set the parameter
OpModeTest
to
On
.
1. Check the Application Configuration: verify that hardware voltage and current
channels of the IED are properly connected to SMAI function blocks, and that
the proper analog outputs of SMAI’s are connected to the analog inputs of the
function block OOSPPAM.
2. Connect three-phase voltage channels of the test set to the appropriate IED
terminals.
3. Connect in parallel two groups of three-phase currents of the test set to the
appropriate IED terminals.
4. Connect the appropriate trip output of the IED to the input channel of the test
set that monitors the trip.
5. Go to
Main menu/Settings/IED Settings/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1
, and make sure that the
function is enabled, that is,
Operation
is set to
On
.
11.4.12.2
Test of point RE (R
FwdR
, X
FwdX
)
GUID-911D370F-8767-4D6C-9621-8663DD26006C v1
The trajectory of the impedance does not enter the lens
characteristic.
GUID-5C5E9BEB-AA60-474E-ACEC-B972ACFE6FA2 v1
Preliminary steady state test at 50 Hz
GUID-8F95CCCC-3282-48E8-9F5E-3F3E77CCCAAE v1
•
Go to
Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs
to check the available
service values of the function block OOSPPAM.
•
Apply the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V
V
V
V
V
ts
t FwdZ
VT s
VT p
=
×
×
=
×
×
=
1 1
1 1 11931
0 1
13 8
95 1
.
.
.
.
.
,
,
,
EQUATION14057 V1 EN-US
(Equation 20)
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
154
Line differential protection RED670 2.2 IEC
Commissioning manual
Summary of Contents for RED670 Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Page 2: ......
Page 18: ...12 ...
Page 36: ...30 ...
Page 68: ...62 ...
Page 72: ...66 ...
Page 108: ...102 ...
Page 278: ...272 ...
Page 282: ...276 ...
Page 288: ...282 ...
Page 306: ...300 ...
Page 307: ...301 ...