Table 28:
Test points for phase-to-earth loop L3-E (Ohm/loop)
Test point
Value
Comments
1
X
[X1+XN]
XN=(X
0
-X
1
)/3
R
0
2
X
0
R
RLdFw
3
X
0.85·[X1+XN]
R≈0.491·(X1+XN)+RFFwPE
R
0.85·[X1+XN]·1/tan(60°)+RFFwPE
4
X
0.85·[X1+XN]
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
5
X
RFFwPE·tan (ArgLd)
R
RFFwPE
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
The table showing test points for phase-to-earth loops is used together with figure
Table 29:
Test points for phase-to-phase loops L1–L2
Test point
Value
Comments
1
X
X1
R
0
2
X
0
R
RLdFw
3
X
0.85·X1
R=0.491·X1+0.5 RFFwPP
R
0.85·X1·1/tan(60°)+0.5 RFFwPP
4
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
5
X
0.5·RFFwPP·tan (ArgLd)
R
0.5·RFFwPP
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
The table showing test points for phase-to-phase loops is used together with figure
11.4.6.1
Measuring the operating limit of set values
GUID-B1B7DEB6-7BC3-4A90-8D8F-E4E69B434AFA v3
Procedure:
Section 11
1MRK 505 378-UEN A
Testing functionality by secondary injection
130
Line differential protection RED670 2.2 IEC
Commissioning manual
Summary of Contents for RED670 Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Page 2: ......
Page 18: ...12 ...
Page 36: ...30 ...
Page 68: ...62 ...
Page 72: ...66 ...
Page 108: ...102 ...
Page 278: ...272 ...
Page 282: ...276 ...
Page 288: ...282 ...
Page 306: ...300 ...
Page 307: ...301 ...