18.8.6
Function status fault protection for IEC 60870-5-103
I103FLTPROT
18.8.6.1
Functionality
GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to
a correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that
is triggering the Disturbance Recorder and the respective configured signal to the
IEC 60870-5-103 I103FLTPROT.
18.8.6.2
Identification
GUID-55593EC4-7AED-47A0-8311-DB22D013A193 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function status fault protection for IEC
60870-5-103
I103FLTPROT
-
-
Section 18
1MRK 505 394-UEN A
Station communication
712
Line differential protection RED650 2.2 IEC
Technical manual