Section 14
Logic
14.1
Tripping logic SMPPTRC
IP14576-1 v4
14.1.1
Identification
SEMOD56226-2 v7
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tripping logic
SMPPTRC
1 -> 0
IEC15000314 V1 EN-US
94
14.1.2
Functionality
M12275-3 v12
A function block for protection tripping and general start indication is always
provided as a basic function for each circuit breaker. It provides a settable pulse
prolongation time to ensure a trip pulse of sufficient length, as well as all
functionality necessary for correct co-operation with autoreclosing functions.
The trip function block includes a settable latch function for the trip signal and
circuit breaker lockout.
The trip function can collect start and directional signals from different application
functions. The aggregated start and directional signals are mapped to the IEC
61850 logical node data model.
1MRK 505 394-UEN A
Section 14
Logic
Line differential protection RED650 2.2 IEC
431
Technical manual