12.4.4.1
Functionality
M13447-3 v8
The Bay control (QCBAY) function is used together with Local remote and local
remote control functions to handle the selection of the operator place per bay.
QCBAY also provides blocking functions that can be distributed to different
apparatuses within the bay.
12.4.4.2
Function block
M13469-3 v4
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
STA
REM
IEC10000048-3-en.vsdx
IEC10000048 V3 EN-US
Figure 166:
QCBAY function block
12.4.4.3
Signals
PID-4086-INPUTSIGNALS v8
Table 186:
QCBAY Input signals
Name
Type
Default
Description
LR_OFF
BOOLEAN
0
External Local/Remote switch is in Off position
LR_LOC
BOOLEAN
0
External Local/Remote switch is in Local position
LR_REM
BOOLEAN
0
External Local/Remote switch is in Remote
position
LR_VALID
BOOLEAN
0
Data representing the L/R switch position is valid
BL_UPD
BOOLEAN
0
Steady signal to block the position updates
BL_CMD
BOOLEAN
0
Steady signal to block the command
PID-4086-OUTPUTSIGNALS v8
Table 187:
QCBAY Output signals
Name
Type
Description
PSTO
INTEGER
Value for the operator place allocation
UPD_BLKD
BOOLEAN
Update of position is blocked
CMD_BLKD
BOOLEAN
Function is blocked for commands
LOC
BOOLEAN
Local operation allowed
STA
BOOLEAN
Station operation allowed
REM
BOOLEAN
Remote operation allowed
Section 12
1MRK 505 394-UEN A
Control
354
Line differential protection RED650 2.2 IEC
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...