21.11
Test mode functionality TESTMODE
IP1647-1 v3
21.11.1
Application
M11407-3 v9
The protection and control IEDs may have a complex configuration with many
included functions. To make the testing procedure easier, the IEDs include the
feature that allows individual blocking of a single-, several-, or all functions.
This means that it is possible to see when a function is activated or trips. It also
enables the user to follow the operation of several related functions to check
correct functionality and to check parts of the configuration, and to check parts.
21.11.1.1
IEC 61850 protocol test mode
GUID-82998715-6F23-4CAF-92E4-05E1A863CF33 v5
The function block TESTMODE has implemented the extended testing mode
capabilities for IEC 61850 Ed2 systems. Operator commands sent to the function
block TESTMODE determine the behavior of the functions. The command can be
given remotely from an IEC 61850 client or from the LHMI under the
Main menu/
Test/Function test modes/Communication/Station Communication/IEC61850
LD0 LLN0/LD0LLN0:1
. The possible values of the function block TESTMODE
are described in
Communication protocol manual, IEC 61850 Edition 1
and
Edition 2
.
There is no setting in PCM600 via PST for the TESTMODE function block.
To be able to set the function block TESTMODE remotely, the
setting via path on LHMI and in PST:
Main menu/Configuration/
Communication/ Station Communication/IEC61850-8-1/
IEC61850-8-1:1RemoteModControl
may not be set to
Off
. The
possible values of the parameter
RemoteModControl
are
Off
,
Maintenance
or
All levels
. The
Off
value denies all access to
function block TESTMODE from remote,
Maintenance
requires
that the category of the originator (orCat) is
Maintenance
and
All
levels
allow any orCat.
The DataObject Mod of the Root LD.LNN0 can be set on the LHMI under
Main
menu/Test/Function test modes/Communication/Station communication/
IEC61850 LD0 LLN0/LD0LLN0:1
to
On
,
Off
,
TestBlocked
,
Test
or
Blocked
.
When the setting of the DataObject Mod is changed at this level, all Logical Nodes
inside the logical device update their own behavior according to IEC61850-7-4.
The supported values of the function block TESTMODE are described in
Communication protocol manual, IEC 61850 Edition 2
. When the function block
TESTMODE is in test mode the Start LED on the LHMI is turned on with steady
light.
1MRK 505 393-UEN B
Section 21
Basic IED functions
Line differential protection RED650 2.2 IEC
415
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...