power swing logic provides the possibility for selective tripping of faults on power
lines during system oscillations (power swings or pole slips) when the distance
protection function should normally be blocked.
Disturbance recording and fault locator are available to allow independent post-
fault analysis after primary disturbances.
One pre-configured package has been defined for the following application:
•
Single breaker, 2/3 line ends, 1/3 phase tripping (A11)
The package is configured and ready for direct use. Analog and control circuits
have been pre-defined and other signals need to be applied as required for each
application. The pre-configured IED can be changed and adapted to suit specific
applications with the application configuration tool.
Forcing of binary inputs and outputs is a convenient way to test wiring in
substations as well as testing configuration logic in the IEDs. Basically it means
that all binary inputs and outputs on the IED I/O modules (BOM, BIM and IOM)
can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a
secure solution for enforcing access control to IEDs and other systems within a
substation. This incorporates management of user accounts, roles and certificates
and the distribution of such, a procedure completely transparent to the user.
The Flexible Product Naming allows the customer to use an IED-vendor
independent IEC 61850 model of the IED. This customer model will be used as the
IEC 61850 data model, but all other aspects of the IED will remain unchanged
(e.g., names on the local HMI and names in the tools). This offers significant
flexibility to adapt the IED to the customers' system and standard solution.
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1
The following tables list all the functions available in the IED.
Those functions that are not exposed to the user or do not need to
be configured are not described in this manual.
2.2
Main protection functions
GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v13
Table 2:
Example of quantities
2
= number of basic instances
0-3
= option quantities
3-A03
= optional function included in packages A03 (refer to ordering details)
Section 2
1MRK 505 393-UEN B
Application
28
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...