Table 23:
Possible cause values from XLNPROXY
Cause
No
Cause Description
Conditions
8
Blocked-by-Mode
The BEH input is 5.
2
Blocked-by-switching-hierarchy
The LOC input indicates that only local commands are
allowed for the breaker IED function.
-24
Blocked-for-open-cmd
The BLKOPN is active indicating that the switch is
blocked for open commands.
-25
Blocked-for-close-cmd
The BLKCLS is active indicating that the switch is
blocked for close commands.
9
Blocked-by-process
If the Blk input is connected and active indicating that the
switch is dynamically blocked. Or if the OPCAP input is
connected, it indicates that the operation capability of the
switch is not enough to perform the command.
5
Position-reached
Switch is already in the intended position.
-31
Switch-not-start-moving
Switch did not start moving within tStartMove.
-32
Persistent-intermediate-state
The switch stopped in intermediate state for longer than
tIntermediate.
-33
Switch-returned-to-init-pos
Switch returned to the initial position.
-34
Switch-in-bad-state
Switch is in a bad position.
-35
Not-expected-final-position
Switch did not reach the expected final position.
The OPCAP input and output are used for the CBOpCap data of a
XCBR respectively SwOpCap for a XSWI. The interpretation for
the command following is controlled through the setting
SwitchType
.
12.3.6
Interaction between modules
M16626-3 v9
A typical bay with apparatus control function consists of a combination of logical
nodes or functions that are described here:
•
The Switch controller (SCSWI) initializes all operations for one apparatus. It
is the command interface of the apparatus. It includes the position reporting as
well as the control of the position
•
The Circuit breaker (SXCBR) is the process interface to the circuit breaker for
the apparatus control function.
•
The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses,
such as operator place selection and blockings for the complete bay.
•
The Protection trip logic (SMPPTRC) connects the "trip" outputs of one or
more protection functions to a common "trip" to be transmitted to SXCBR.
•
The Autorecloser (SMBRREC) consists of the facilities to automatically close
a tripped breaker with respect to a number of configurable conditions.
•
The logical node Interlocking (SCILO) provides the information to SCSWI
whether it is permitted to operate due to the switchyard topology. The
Section 12
1MRK 505 393-UEN B
Control
262
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...