which is normally set to the nominal voltage level (phase-to-phase) of the power
system or the high voltage equipment under consideration.
The time delay for the OV2PTOV can sometimes be critical and related to the size
of the overvoltage - a power system or a high voltage component can withstand
smaller overvoltages for some time, but in case of large overvoltages the related
equipment should be disconnected more rapidly.
Some applications and related setting guidelines for the voltage level are given
below:
The hysteresis is for overvoltage functions very important to prevent that a
transient voltage over set level is not “sealed-in” due to a high hysteresis. Typical
values should be ≤ 0.5%.
9.2.3.1
Equipment protection, such as for motors, generators, reactors and
transformers
M13852-10 v3
High voltage will cause overexcitation of the core and deteriorate the winding
insulation. The setting has to be well above the highest occurring "normal" voltage
and well below the highest acceptable voltage for the equipment.
9.2.3.2
Equipment protection, capacitors
M13852-13 v1
High voltage will deteriorate the dielectricum and the insulation. The setting has to
be well above the highest occurring "normal" voltage and well below the highest
acceptable voltage for the capacitor.
9.2.3.3
Power supply quality
M13852-16 v1
The setting has to be well above the highest occurring "normal" voltage and below
the highest acceptable voltage, due to regulation, good practice or other
agreements.
9.2.3.4
High impedance earthed systems
M13852-19 v6
In high impedance earthed systems, earth-faults cause a voltage increase in the
non-faulty phases. Two step overvoltage protection (OV2PTOV) is used to detect
such faults. The setting must be above the highest occurring "normal" voltage and
below the lowest occurring voltage during faults. A metallic single-phase earth-
fault causes the non-faulted phase voltages to increase a factor of √3.
9.2.3.5
The following settings can be done for the two step overvoltage
protection
M13852-22 v10
ConnType
: Sets whether the measurement shall be phase-to-earth fundamental
value, phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-
phase RMS value.
Section 9
1MRK 505 393-UEN B
Voltage protection
194
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...