15.2.7
Time synchronization via IRIG-B
15.2.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization via IRIG-B
IRIG-B
-
-
15.2.7.2
Settings
Table 496:
IRIG-B Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
TimeDomain
LocalTime
UTC
-
-
LocalTime
Time domain
Encoding
IRIG-B
1344
1344TZ
-
-
IRIG-B
Type of encoding
TimeZoneAs1344
MinusTZ
PlusTZ
-
-
PlusTZ
Time zone as in 1344 standard
15.2.8
Operation principle
15.2.8.1
General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time the
clock is intended to have. Clock accuracy indicates the increase in error, that is, the time
gained or lost by the clock. A disciplined clock knows its own faults and tries to
compensate for them.
Section 15
1MRK 511 287-UUS A
Basic IED functions
594
Technical manual