![ABB REC650 ANSI Technical Manual Download Page 442](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772442.webp)
Table 360:
VMSQI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
3V0ZeroDb
0 - 100000
m%
1
500
Zero point clamping
3V0HiHiLim
0 - 2000000
V
1
288000
High High limit (physical value)
3V0HiLim
0 - 2000000
V
1
258000
High limit (physical value)
3V0LowLim
0 - 2000000
V
1
213000
Low limit (physical value)
3V0LowLowLim
0 - 2000000
V
1
198000
Low Low limit (physical value)
V1ZeroDb
0 - 100000
m%
1
500
Zero point clamping
V1HiHiLim
0 - 2000000
V
1
96000
High High limit (physical value)
V1HiLim
0 - 2000000
V
1
86000
High limit (physical value)
V1LowLim
0 - 2000000
V
1
71000
Low limit (physical value)
V1LowLowLim
0 - 2000000
V
1
66000
Low Low limit (physical value)
V1LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
V2ZeroDb
0 - 100000
m%
1
500
Zero point clamping
V2HiHiLim
0 - 2000000
V
1
96000
High High limit (physical value)
V2HiLim
0 - 2000000
V
1
86000
High limit (physical value)
V2LowLim
0 - 2000000
V
1
71000
Low limit (physical value)
V2LowLowLim
0 - 2000000
V
1
66000
Low Low limit (physical value)
12.1.6.5
Monitored data
Table 361:
VMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
3V0
REAL
-
kV
3U0 Amplitude
3V0ANGL
REAL
-
deg
3U0 Angle
V1
REAL
-
kV
U1 Amplitude
V1ANGL
REAL
-
deg
U1 Angle
V2
REAL
-
kV
U2 Amplitude
V2ANGL
REAL
-
deg
U2 Angle
Section 12
1MRK 511 287-UUS A
Monitoring
436
Technical manual