12.7
Disturbance report
12.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report
DRPRDRE
-
-
Analog input signals
A1RADR
-
-
Analog input signals
A2RADR
-
-
Analog input signals
A3RADR
-
-
Analog input signals
A4RADR
-
-
Binary input signals
B1RBDR
-
-
Binary input signals
B2RBDR
-
-
Binary input signals
B3RBDR
-
-
Binary input signals
B4RBDR
-
-
Binary input signals
B5RBDR
-
-
Binary input signals
B6RBDR
-
-
12.7.2
Application
To get fast, complete and reliable information about disturbances in the primary and/or in
the secondary system it is very important to gather information on fault currents, voltages
and events. It is also important having a continuous event-logging to be able to monitor in
an overview perspective. These tasks are accomplished by the disturbance report function
DRPRDRE and facilitate a better understanding of the power system behavior and related
primary and secondary equipment during and after a disturbance. An analysis of the
recorded data provides valuable information that can be used to explain a disturbance,
basis for change of IED setting plan, improve existing equipment, and so on. This
information can also be used in a longer perspective when planning for and designing new
installations, that is, a disturbance recording could be a part of Functional Analysis (FA).
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of all
selected analog and binary signals connected to the function blocks that is,
•
maximum 30 external analog signals,
•
10 internal derived analog signals, and
•
96 binary signals.
Disturbance report function is a common name for several functions that is, Indications,
Event recorder, Sequential of events, Trip value recorder, Disturbance recorder.
1MRK 511 286-UUS A
Section 12
Monitoring
295
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...