en04000501_ansi.vsd
289OPTR (bay 1/sect.B1)
S1DC_OP
VPS1_DC
EXDU_BB
AND
289OPTR (bay n/sect.B1)
. . .
. . .
. . .
VP289TR (bay 1/sect.B1)
VP289TR (bay n/sect.B1)
EXDU_DB (bay 1/sect.B1)
EXDU_DB (bay n/sect.B1)
. . .
. . .
. . .
. . .
. . .
. . .
AND
AND
ANSI04000501 V1 EN
Figure 109:
Signals from double-breaker bays in section B1 to a bus-section
disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
en04000502_ansi.vsd
289OPTR (bay 1/sect.B2)
S2DC_OP
VPS2_DC
EXDU_BB
AND
289OPTR (bay n/sect.B2)
. . .
. . .
. . .
VP289TR (bay 1/sect.B2)
VP289TR (bay n/sect.B2)
EXDU_DB (bay 1/sect.B2)
EXDU_DB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
AND
AND
ANSI04000502 V1 EN
Figure 110:
Signals from double-breaker bays in section B2 to a bus-section
disconnector
10.4.6.4
Signals in breaker and a half arrangement
If the busbar is divided by bus-section disconnectors, the condition for the busbar
disconnector bay
no other disconnector connected to the bus-section
must be made by a
project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-
section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding
signals from busbar B are used.
Section 10
1MRK 511 286-UUS A
Control
244
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...