point and ground (current transformer located in the WYE point of a WYE
connected transformer winding).
•
For some special line protection applications this dedicated IED CT input
can be connected to parallel connection of current transformers in all three
phases (Holm-Green connection).
2. calculated from three phase current input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) function
analog input I3PPOL is NOT connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I
0
from the first
three inputs into the pre-processing block by using the following formula:
3
= ×
=
+
+
Pol
I
Io
IA IB IC
EQUATION2019-ANSI V1 EN
(Equation 15)
where:
IA, IB and IC are fundamental frequency phasors of three individual phase currents.
The Negative sequence current can be calculated from the three-phase current input
within the IED by using the pre-processing block. The pre-processing block will
calculate the negative sequence current from the three inputs into the pre-processing
block by using the following formula:
2
I2 = (IA+
IB+
IC)/3
a
a
×
×
GUID-65EF3644-BDC6-4E4B-97B0-AA48929C4CAF V1 EN
(Equation 16)
where:
IA, IB and IC are fundamental frequency phasors of three individual phase currents.
alpha
is 1 with an angle of 120 degrees
This phasor is used together with the phasor of the polarizing quantity in order to
determine the direction of the ground fault (Forward/Reverse).
7.2.7.4
External polarizing for ground-fault function
The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKn(where x indicates
the relevant step within the protection) to provide external directional control (that is,
torque control) by for example using one of the following functions if available in the
IED:
1MRK 505 277-UUS C
Section 7
Current protection
93
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...