15.12.4.1
Authorization handling in the IED
At delivery the default user is the SuperUser. No Log on is required to operate the IED
until a user has been created with the IED User Management..
Once a user is created and written to the IED, that user can perform a Log on, using the
password assigned in the tool. Then the default user will be Guest.
If there is no user created, an attempt to log on will display a message box: “No user
defined!”
If one user leaves the IED without logging off, then after the timeout (set in
Main
menu/Configuration/HMI/Screen/1:SCREEN
) elapses, the IED returns to Guest
state, when only reading is possible. By factory default, the display timeout is set to 60
minutes.
If one or more users are created with the IED User Management and written to the
IED, then, when a user attempts a Log on by pressing the
key or when the user
attempts to perform an operation that is password protected, the Log on window opens.
The cursor is focused on the User identity field, so upon pressing the
key, one can
change the user name, by browsing the list of users, with the “up” and “down” arrows.
After choosing the right user name, the user must press the
key again. When it
comes to password, upon pressing the
key, the following characters will show up:
“
✳✳✳✳✳✳✳✳
”. The user must scroll for every letter in the password. After all the
letters are introduced (passwords are case sensitive) choose OK and press the
key
again.
At successful Log on, the local HMI shows the new user name in the status bar at the
bottom of the LCD. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the Log
on has failed, an "Error Access Denied" message opens. If a user enters an incorrect
password three times, that user will be blocked for ten minutes before a new attempt to
log in can be performed. The user will be blocked from logging in, both from the local
HMI and PCM600. However, other users are to log in during this period.
15.13
Authority status ATHSTAT
15.13.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Authority status
ATHSTAT
-
-
1MRK 505 277-UUS C
Section 15
Basic IED functions
411
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...