It is important for indication in the SLD that the a symbol is associated
with a controllable object, otherwise the symbol won't be displayed on
the screen. A symbol is created and configured in GDE tool in PCM600.
The PSTO input is connected to the Local remote switch to have a selection of
operators place, operation from local HMI (Local) or through IEC 61850 (Remote). An
INTONE connection from Fixed signal function block (FXDSIGN) will allow
operation from local HMI.
As it can be seen, both indications and commands are done in double-bit
representation, where a combination of signals on both inputs/outputs generate the
desired result.
The following table shows the relationship between IPOS1/IPOS2 inputs and the name
of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1
IPOS2
Name of displayed string Default string value
0
0
PosUndefined
P00
1
0
Position1
P01
0
1
Position2
P10
1
1
PosBadState
P11
10.4
IEC 61850 generic communication I/O functions
DPGGIO
10.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
DPGGIO
-
-
10.4.2
Functionality
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send double indications to other systems or equipment in the substation. It is
especially used in the interlocking and reservation station-wide logics.
Section 10
1MRK 505 277-UUS C
Control
172
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...