Planning the electrical installation 41
Protecting in short-circuit situation and against thermal
overload
Protecting the inverter and AC output cable in short-circuit
situations
The inverter has internal AC fuses or optionally an AC breaker which restrict inverter
damage in case of a short-circuit in the inverter. Install external protection (such as fuses)
according to local regulations, appropriate AC line voltage and the rated current of the
inverter to protect the AC output cable.
Protecting the photovoltaic generator and DC input cable in short-
circuit situations
The input DC fuses protect the inverter DC circuit and the DC input cables in a short-circuit
situation when the cable is dimensioned according to inverter nominal DC current and fuse
ratings. Refer to chapter
on page
To protect inverters delivered without input DC fuses (0F291), obey the
instructions in section
Inverters without input DC fuses (0F291)
on page
For the recommended DC input fuse options, refer to
page
.
Note
: The inverter does not protect the photovoltaic generator. Install adequate protection
devices to, for example, each string.
Protecting the inverter and the AC output cable against thermal
overload
The inverter protects itself and the AC output cable against thermal overload when the
cable is dimensioned according to the nominal current of the inverter. No additional
thermal protection devices are needed.
Protecting the DC input cable against thermal overload
The input DC fuses protect the DC input cables against thermal overload when the cable is
dimensioned according to inverter input DC fuse ratings. Refer to chapter
on page
.
To protect inverters delivered without input DC fuses (0F291), obey the
instructions in section
Inverters without input DC fuses (0F291)
on page
For the recommended DC input fuse options, refer to
page
.
When the option (+G417) for DC input current monitoring is selected, the DC input cable
current can be monitored with SCADA or an automation system to achieve additional
protection.
Summary of Contents for PVS800-57B
Page 1: ... ABB SOLAR INVERTERS PVS800 57B central inverters Hardware manual ...
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 Safety instructions ...
Page 30: ...30 Operation principle and hardware description ...
Page 32: ...32 Planning the mechanical installation ...
Page 62: ...62 Dimension drawings Cabinet dimensions ...
Page 63: ...Dimension drawings 63 ...
Page 64: ...64 Dimension drawings Cabinet attachment points ...
Page 65: ...Dimension drawings 65 ...
Page 66: ...66 Dimension drawings AC and DC cabling lead throughs ...
Page 67: ...Dimension drawings 67 ...
Page 68: ...68 Dimension drawings AC cabling ...
Page 69: ...Dimension drawings 69 ...
Page 70: ...70 Dimension drawings DC cabling ...
Page 71: ...Dimension drawings 71 ...
Page 72: ...72 Dimension drawings ...