Electrical installation 93
Default I/O connection diagram (RDCU – A41)
The external control cable connections to the RMIO board for the PVS800 solar inverter
control program with default settings are shown below (program version ISXR7360 and
later).
RMIO
X20
1
VREF-
By default, not in use. -10 V DC, 1 kohm <
R
L
< 10 kohm
2
AGND
X21
1
VREF+ By default, not in use. 10 V DC, 1 kohm <
R
L
< 10 kohm
2
AGND
3
AI1+
Insulation resistance measurement
0 … 10 V (Q954),
R
in
= 200 kohm
4
AI1-
5
AI2+
AC cubicle ambient temperature
measurement 4...20 mA -30…+80 °C.
6
AI2-
7
AI3+
DC cubicle ambient temperature
measurement. 4...20 mA -30…+80 °C.
8
AI3-
9
AO1+
Fan speed control for LCL filters.
0(4)…20 mA,
R
L
< 700 ohm
10
AO1-
11
AO2+
By default, not in use. 0(4)…20 mA,
R
L
<
700 ohm
12
AO2-
X22
1
DI1
Fan acknowledgement and LCL filter
temperature supervision
2
DI2
Run enable. 0 = Inverter run is disabled
1 = Inverter run is enabled
3
DI3
Status of the AC contactor K1.1.
0 = Open, 1 = Closed
4
DI4
Ground fault supervision (oQ954,
+Q976 and +Q981)
5
DI5
By default, not in use.
6
DI6
Status of the 24 V auxiliary power buffer.
0 = Buffer is not full, 1 = Buffer is full
7
+24VD
+24 V DC max. 100 mA
8
+24VD
9
DGND1 Digital ground
10
DGND2 Digital ground
11
DIIL
By default, not in use.
X23
1
+24V
Auxiliary voltage output and input, non-
isolated, 24 V DC 250 mA
1)
2
GND
X25
1
RO1
Relay output 1: Charging contactor
control
2
RO1
3
RO1
X26
1
RO2
Relay output 2: Control of the AC
contactor K1.3
2
RO2
3
RO2
X27
1
RO3
Relay output 3: Control of the AC
contactor K1 / K1.1.
2
RO3
3
RO3
Terminal block size:
cables 0.3 to 3.3 mm
2
(22 to 12 AWG)
Tightening torque:
0.2 to 0.4 N·m
(0.2 to 0.3 lbf·ft)
1) Total maximum current shared
between this output and the
optional modules installed on the
board.
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...