92 Electrical installation
Default I/O connection diagram (RDCU – A43)
The external control cable connections to the RMIO board for the PVS800 solar inverter
master control program with default settings are shown below (program version
GSXR7360 and later).
RMIO
X20
1
VREF-
Reference voltage -10 V DC, 1 kohm <
R
L
< 10 kohm
2
AGND
X21
1
VREF+ Reference voltage 10 V DC, 1 kohm <
R
L
<
10 kohm
2
AGND
3
AI1+
DC current measurement -10 … 10 V
4
AI1-
5
AI2+
Grounding current measurement.
4…20 mA
, R
in
= 100 ohm
4)
6
AI2-
7
AI3+
Solar generator DC voltage measurement.
0(4)…20 mA
, R
in
= 100 ohm
8
AI3-
9
AO1+
By default, not in use. 0(4)…20 mA,
R
L
<
700 ohm
10
AO1-
11
AO2+
By default, not in use. 0(4)…20 mA,
R
L
<
700 ohm
12
AO2-
X22
1
DI1
Reset
2
DI2
By default, not in use.
1)
3
DI3
AC and DC overvoltage protection
4
DI4
DC cable overcurrent protection
5
DI5
By default, not in use
5)
6
DI6
Status of the emergency stop circuit
7
+24VD
+24 V DC max. 100 mA
8
+24VD
9
DGND1 Digital ground
10
DGND2 Digital ground
11
DIIL
DC grounding acknowledgement
4)
X23
1
+24V
Auxiliary voltage output and input, non-
isolated, 24 V DC 250 mA
2)
2
GND
X25
1
RO1
Relay output 1: By default, not in
use. With Q951 reserved.
3)
2
RO1
3
RO1
X26
1
RO2
Relay output 2: Fault indication
6)
1 = No fault
0 = Fault
2
RO2
3
RO2
X27
1
RO3
Relay output 3: Grounding switch
control
4)
2
RO3
3
RO3
Terminal block size:
cables 0.3 to 3.3 mm
2
(22 to 12 AWG)
Tightening torque:
0.2 to 0.4 N·m
(0.2 to 0.3 lbf·ft)
1) Can be configured for Start/Stop or
other use with parameter settings.
2) Total maximum current shared
between this output and the optional
modules installed on the board.
3) Can be configured with parameter
settings for resetting the emergency
stop circuit with the emergency stop
reset button on the cabinet door
(Q951 in PVS800-57-0100kW,
-0250kW and -0315kW units).
4) Used only with oF282 and
+F283.
5) Transformer trip (MWS)
6) Can be configured with parameter
66.03 DO2.
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...