78 Planning the electrical installation
Signals in separate cables
Run analog and digital signals in separate, shielded cables.
Never mix 24 V DC and 115/230 V AC signals in the same cable.
Signals allowed to be run in the same cable
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in the
same cables as digital input signals. It is recommended that the relay-controlled signals be
run as twisted pairs.
Relay cable type
The cable type with braided metallic screen (eg, ÖLFLEX by LAPPKABEL, Germany) has
been tested and approved by ABB.
Installation sites above 2000 metres (6560 feet)
WARNING!
Protect against direct contact when installing, operating and servicing
the RMIO board wiring and optional modules attached to the board. The
Protective Extra Low Voltage (PELV) requirements stated in EN 50178 are not
fulfilled at altitudes above 2000 m (6560 ft).
Routing the cables
It is recommended that the input DC power cable, output AC power cable and control
cables be installed on separate trays.
Where control cables must cross power cables ensure they are arranged at an angle as
near to 90 degrees as possible. Do not run extra cables through the inverter.
The cable trays must have good electrical bonding to each other and to the grounding
electrodes. Aluminium tray systems can be used to improve local equalizing of potential.
If four conductor AC cabling is used, place the three output phase cables symmetrically
and close to each other. Asymmetrical installation may induce current to grounding cables
and metal structures.
A diagram of the cable routing is shown below.
90 °
DC input cable
AC output power cable
Control cables
min 500 mm (19.7 in.)
Inverter
min 500 mm (19.7 in.)
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...