74 Planning the electrical installation
Requirements for the transformer
•
suitable for the network and inverter AC voltage, current and power
•
suitable for use with IGBT inverters
•
degree of protection, temperature limits and lifetime are appropriate for the
environment
•
equipped with a static grounded screen between the high and low voltage windings
•
voltage withstand level of the low voltage winding is at least 1.6 kV against ground. A
typical voltage waveform against ground is shown below.
•
voltage rise time withstand level (d
u
/d
t
) of the low voltage winding is at least 1000 V
per microsecond against ground.
•
recommended rated short-circuit impedance (X
k
) for each inverter is approximately
6% (±1%)
•
withstands low-voltage side current DC components of at least 0.5% of the nominal
rated current preferably without using an air gap
•
withstands the 3% total harmonic distortion generated by the inverter. However, we
recommend dimensioning the transformer for at least 5% total harmonic distortion to
withstand possible outside interference from the network.
ABB recommends that the transformer is equipped with an off-load tap changer for voltage
regulation on the high-voltage side of the winding with two 2.5% step points to the plus and
minus directions.
The inverter does not require any specific transformer notation. ABB recommends using
traditional notations, such as Dy11d0, Dy11y11, etc.
Do not ground the neutral (star) point of the transformer or connect it to the neutral points
of other windings.
t
(ms)
U
AC-grid
(V)
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...