60 Operation principle and hardware description
Types -0500kW-A to -1000kW-C
Selection
Alternatives
Product series
PVS800 product series (ABB central inverters)
Type
57
Cabinet-built central inverter. When no options are selected: IP42 (UL
Type 2), AC main contactor, gPV fuses, AC side switch disconnector,
terminals for 230 V AC external control voltage, CDP312 control panel,
RDCO-03 module for optical communication, CE-marked according to
LV and EMC, PVS800 solar inverter control programs, bottom entry and
exit of cables, coated boards, maximum DC voltage 1100 V DC,
ungrounded DC input, IT (ungrounded) AC output, DC input overvoltage
and surge protection (type 1+2), AC output overvoltage protection with
varistors, AC grounding terminals on output busbars, DC input busbars
(number of DC inputs must be selected with a plus code),
DC contactor
and main switch, DC grounding terminals on input busbars, grid support
functions (Low voltage ride-through disables anti-islanding functionality,
Reactive power production during the night), a set of manuals, warranty
12/24 months.
Nominal AC power
xxxkW
Refer to
the rating tables, page
.
Voltage
B
350 V AC (operational [MPPT] DC voltage range 525…825 V DC)
C
400 V AC (operational [MPPT] DC voltage range 600…850 V DC)
+ options
Filters
E216
EMC/RFI filter for the network side of the transformer on TN (grounded)
low voltage networks
Cabinet and construction
options
C175
Container option for PVS800-IS
Must be selected for PVS800-IS
PVS1 and PVS2.
C176
Doors with hinges on the left side
C178
VDE approved
G300
Cabinet heater
G396
Auxiliary power supply, 100 V
Only one of options G396, G397,
G398 can be selected. If option
G415 is selected, options G396,
G397, G398 cannot be selected.
G397
Auxiliary power supply, 115 V
G398
Auxiliary power supply, 200 V
G410
Junction box power supply
G415
Auxiliary power supply from main circuit
G416
Current transducers for all DC inputs. Voltage signals to an external
controller.
G417
Current transducers for all DC inputs. Internally monitored and
supervised.
Line options
F263
Advanced AC output overvoltage and surge protection
F282
Grounding, positive DC
F283
Grounding, negative DC
0F291
No input DC fuses
Cabling
4H382
4 × fuse-protected DC input connections for 500 kW and 630 kW units
5H382
5 × fuse-protected DC input connections for 500 kW and 630 kW units
8H382
8 × fuse-protected DC input connections for 500 kW, 630 kW, 875 kW
and 1000 kW units
10H382 10 × fuse-protected DC input connections for 500 kW, 630 kW, 875 kW
and 1000 kW units
12H382 12 × fuse-protected DC input connections for 500 kW, 630 kW, 875 kW
and 1000 kW units
15H382 15 × fuse-protected DC input connections for 500 kW, 630 kW, 875 kW
and 1000 kW units
16H382 16 × fuse-protected DC input connections for 875 kW and 1000 kW units
20H382 20 × fuse-protected DC input connections for 875 kW and 1000 kW units
Summary of Contents for PVS800-57-0100kW-A
Page 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Page 4: ......
Page 22: ...20 Safety instructions ...
Page 64: ...62 Operation principle and hardware description ...
Page 74: ...72 Mechanical installation ...
Page 90: ...88 Electrical installation PE PE PE ...
Page 124: ...122 Maintenance ...
Page 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Page 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Page 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Page 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Page 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Page 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Page 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Page 178: ...176 Dimension drawings ...
Page 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...