Quickstart PST30...PSTB1050

This document is a short guide to how to connect, do the 
configuration and start the softstarter in the easiest way.

Warning!

Mounting, electrical connection and settings of the 
softstarter shall be made in accordance with existing laws 
and regulations and be performed by authorised personnel.
Do not change any parameters in the Service Settings 
menu.

Connection

1. Mount the softstarter according to Chapter 4 “Mounting“, 

see manual 1SFC132003M0201.

2. Be aware of the ambient temperature. 

Derating is required above 40 

°

C (104 

°

F).

3. Connect the main circuit: terminals 1L1 - 3L2 - 5L3 to the 

line side and terminals 2T1 - 4T2 - 6T3 to the motor side.

4. Connect the supply voltage: terminal 1 and 2 

(100-250V 50/60Hz).

5. Connect the functional ground: terminal 3. 

The wire shall be as short as possible, and be connected to 
the mounting plate.The mounting plate should also be 
earthed.

6. Connect the start/stop circuits: terminal 4, 5, 8, 9 and 10 

according to the diagram. 24V DC only.

7. Check that the main and supply voltage corresponds to 

the softstarter ratings.

8. Switch on the supply voltage.

9. The green "Power on" LED is on and the LCD shall 

appear as in figure 3.

Power on

Protection

Fault

1

2

3

4

1SFC132029F0001

U= 0%

 I=0.0A

Menu

Figure 1:

1

Status indication LEDs

2

LCD display

3

Selection keys for selecting, changing 
and storing parameters

4

Navigation keys for navigating in the 
menus
Arrows shown in the display indicates 
that the value/menu is possible to 
change or scroll

L1

L2

L3

N

KM1

1L1 3L2 5L3

2T1 4T2 6T3

6 7

8 9

12 13 14 15 16 17 18 19 20

U V W

1 2

3

4 5

4 5

10

M

3

1SFC132030F0001

10 11

Figure 2: Standard connection PST

Start

Start

Start

Stop

Power on

Protection

Fault

Figure 3: Top level

U=

0%

 I=0.0A

Menu