Functions
Chapter 10
142
1SFC132003M0201
10:21 Overload protection, type of
operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/OL Op
This parameter makes it possible to select between three
different actions by the softstarter when the protection is
activated. It is active only if the motor overload protection is
selected.
Stop–M
The motor stops and a manual reset is required
before restart.
Stop–A
The motor stops and an automatic reset is
performed when the fault disappears
(motor temp. <80%)
Ind
The motor continues to run but a fault indication
is given.
Parameter
text
Default value Setting range
Description
OL Op
Stop–M
Stop–M, Stop–A,
Ind
Type of opera-
tion for over-
load protection
Summary of Contents for PST105
Page 2: ...This manual belongs to ...
Page 4: ......
Page 8: ...Chapter 8 1SFC132003M0201 Notes ...
Page 10: ...Introduction 10 1SFC132003M0201 ...
Page 14: ...Introduction Chapter 1 14 1SFC132003M0201 ...
Page 16: ...Quickstart 16 1SFC132003M0201 ...
Page 20: ...Description 20 1SFC132003M0201 ...
Page 34: ...Description Chapter 3 34 1SFC132003M0201 ...
Page 36: ...Mounting 36 1SFC132003M0201 ...
Page 40: ...Mounting Chapter 4 40 1SFC132003M0201 ...
Page 42: ...Connection 42 1SFC132003M0201 ...
Page 60: ...Connection Chapter 5 60 1SFC132003M0201 ...
Page 62: ...Human Machine Interface HMI 62 1SFC132003M0201 ...
Page 74: ...Human Machine Interface HMI Chapter 6 74 1SFC132003M0201 ...
Page 76: ...Setting and configuration 76 1SFC132003M0201 ...
Page 120: ...Fieldbus communication option 120 1SFC132003M0201 ...
Page 124: ...Maintenance 124 1SFC132003M0201 ...
Page 126: ...Maintenance Chapter 9 126 1SFC132003M0201 ...
Page 130: ...Chapter 130 1SFC132003M0201 ...
Page 178: ...Trouble shooting 178 1SFC132003M0201 ...
Page 188: ...Trouble shooting Chapter 11 188 1SFC132003M0201 ...
Page 190: ...Diagrams 190 1SFC132003M0201 ...
Page 199: ......