- 24 -
6.2
PS D(H) with electronic overload protection
6.2.1
Different status on LED's and signal relays
LED on
Signal relay energised
LED off
Signal relay not activated
See
LED's
Signal relays
next
page
Run
TOR
Fault
Over
load
I
OVL
No control voltage on terminal 1 and 2
F1
F2
On
R
T
P
II
OVL
Control voltage supplied
F1
F2
Ready for start
On
R
T
P
III
OVL
a)
Control voltage supplied and start signal is given.
F1
F2
b)
Control voltage supplied and making ramp down
On
R
during stop
T
P
IV
OVL
Normal continuous run.
F1
F2
100% voltage to the motor
On
R
By-pass signal relay energised
T
P
V
OVL
Normal continuous run.
F1
F2
100% voltage to the motor
On
R
By-pass signal relay energised
T
P
Power factor optimising (energy saving) activated
(Switch PF in Y, On-position)
VI
OVL
Control voltage supplied and start signal is given.
F1
Fault F1
See fault codes and flow chart
On
Phase loss
T
Reset
Via stop signal
VII
OVL
Control voltage supplied.
F1
F2
Fault F2
See fault codes and flow chart
On
R
a)
Over temperature on heat sink
T
P
b)
High current switch off
With the switch in position Y (On)
c)
Internal fault P.C.B
Reset
Via stop signal
VIII
OVL
Control voltage supplied.
F1
F2
Fault F1+F2 See fault codes and flow chart
On
R
a)
Shorted thyristor
T
P
b)
Semiconductor not conducting
IX
OVL
Continuous run with shorted thyristor
F1
F2
(Switch PF must be in N-position, Off)
On
R
T
P
X
OVL
Tripped electronic over load
F1
F2
Reset: With the reset button or by closing between
On
R
terminals X2: 24...25
T
P
The start signal has to be removed and the LED
OVL has to flash.