Modifications reserved
Page 46/49
10
Appendix C
Introduction
The battery configuration is described in the following way:
“number of battery strings” x ( “number of 12V battery blocks” x “battery capacity”)
UPS internal battery configuration
UPS Model
Battery configuration
UPS PowerValue 11/31 T 10 kVA
no internal
UPS PowerValue 11/31 T 10 kVA B
1 x ( 24 x 9Ah )
UPS PowerValue 11/31 T 10 kVA B2
2 x ( 24 x 9Ah )
UPS PowerValue 11/31 T 20 kVA
no internal
UPS PowerValue 11/31 T 20 kVA B
2 x ( 24 x 9Ah )
UPS PowerValue 11/31 T 10 kVA S
no internal
UPS PowerValue 11/31 T 20 kVA S
no internal
Standard battery cabinet (4 x 24 x 9 Ah) value setting through LCD display and RS232 (M is the total
nr of standard battery cabinets connected, M≥1)
UPS Model
LCD display (path:
Settings
Password
(USER)
External battery
modules)
RS232
command:
SASV03[value]<cr>
UPS PowerValue 11/31 T 10 kVA
4M – 1
4M
UPS PowerValue 11/31 T 10 kVA B
4M
4M + 1
UPS PowerValue 11/31 T 10 kVA B2
4M + 1
4M + 2
UPS PowerValue 11/31 T 20 kVA
4M – 2
4M
UPS PowerValue 11/31 T 20 kVA B
4M
4M + 2
UPS PowerValue 11/31 T 10 kVA S
4M – 1
4M
UPS PowerValue 11/31 T 20 kVA S
4M - 2
4M