ELECTRICAL INSTALLATION
PRODUCT
PCS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS600000 E40
REV.
G
LANG.
en
PAGE
71/114
6.4.1.3. Cable Shielding, routing and separate earth wires
The shields have to be connected to the earthing busbar next to the converter phase
connections.
– To fulfill EMC requirements, screened cables are mandatory.
– If the cross-section of the cable screen is less than 50% of the cross-section of the phase
conductor, an additional equipotential bonding conductor is required. This conductor is
laid in parallel to the phase conductor.
6.4.2. Grid side
Topic
Value
Unit
Comment
Number of phases
1 × 3 (1CL)
2 × 3 (2CL)
pcs
pcs
Connection
Pfisterer P3PS panel socket
Number of connections
2 or 3
sockets /
phase
Plugs for up to two cables can be
connected. For more information,
see the project
-
specific
documentation.
du/dt
< 2.5
kV
At converter terminals
Rated voltage
3.3
kV
Insulation U
0
/ U
6 / 10
kV
IEEE: 5 / 8 kV
Rating factor
0.85
-
To cover converter operation
Maximum length
150
m
Surge phase current including
DC offset
16.2
kArms
Maximum 500 ms