82
PCS100 UPS-I
User Manual
10.3.2
Menu 000 Electrical Settings
100 Electrical Settings
This menu contains electrical settings for the UPS-I
Parameter:
112 System Current
Function:
Set total rated current of system
–
Line RMS
Access:
Factory Only
Range:
150 A to 5000 A
Units:
Amperes RMS
Factory
Setting:
PCS100 UPS-I rated current. (Displayed on the PCS100 UPS-I rating label)
Parameter:
113 Module Voltage
Function:
Selects the Inverter module operating voltage
Access:
Factory Only
Setting Up:
With the PCS100 UPS-I this parameter is fixed to 480 V
Parameter:
121 Utility Voltage
Function:
Adjusts the PCS100 UPS-I working voltage
Access:
Tech
Range:
Nameplate voltage rating of the PCS100 UPS-I +/- 10%
Units:
Volts RMS
Factory
Setting:
Nameplate voltage rating of PCS100 UPS-I
Setting up:
Set to the supply voltage.
Note
This setting also adjusts the output voltage when the PCS100 UPS-I is operating from the
backup energy storage.
Parameter:
122 Utility Frequency
Function:
Set to frequency of Supply
Access:
Tech
Range:
40 Hz to 60 Hz
Units;
Hz
Factory
Setting:
Nameplate frequency rating of PCS100 UPS-I
Setting up:
Set to the supply frequency.
Parameter:
131 Sag Recording Thres
Function:
Power quality meter sag recording threshold.
Access:
Operator
Range:
0% to
531 RMS Surge Threshold
Units:
% of parameter
121 Utility Voltage
Factory
Setting:
90%
Setting up:
This parameter adjusts the recording threshold for sag events recorded in the event log
and on the summary page. It does not alter the operation of the PCS100 UPS-I. Should be
set the same as or less than parameter
530 RMS Sag Threshold
. If set greater than
530
RMS Sag Threshold
the PQ meter may record part of the pre event sag voltage and give an
erroneous reading.