PCS100 AVC-20
User Manual
21
—
4
TECHNICAL SPECIFICATION
NOTE: These specifications apply to the standard PCS100 AVC-20 range and may be superseded by special
variations stated on the PCS100 AVC-20 rating label or User Manual Addendum.
4.1
Model Range
Power range
250
–
3000 kVA
4.2
Utility
–
Input
Rated voltage (model specific)
400 V
–
application range 380 V - 415 V
Note: Application voltage lower than the rated voltage results in
power derating. Consult the rating tables for more information.
Maximum supply voltage
130%
Nominal supply frequency
50 Hz or 60 Hz
Frequency tolerance
± 5 Hz
Power system
3-phase + Neutral (4-Wire)
Centre ground referenced (TN-S)
Overvoltage category
III
Fault capacity
Refer to the model tables shown in this document.
Outage
–
control ride through
> 600 ms
Harmonics
IEC 61000-2-4 Class 2 (THD
V
< 8%)