4.5.3 Function test of three-position enabling device
Performing the function test
Note
Action
Start the robot system and turn the mode
switch to manual mode.
1
This test is passed if the event message
10011 Motors ON state
appears in the
event log.
Press the three-position enabling device
to the middle position and then hold the
enabling device in this position.
2
If either of the following happens, then the
test is failed and the root cause must be
found:
•
if the event message
10011 Motors
ON state
does not appear
•
if the event message
90780 Two-
channel fault in Safety Controller
appears
This test is passed if the event message
10012 Safety guard stop state
appears in
the event log.
While still holding the three-position en-
abling device pressed, press the enabling
device harder to the enable the device's
third position.
3
If either of the following happens, then the
test is failed and the root cause must be
found:
•
if the event message
10012 Safety
guard stop state
does not appear
•
if the event message
90780 Two-
channel fault in Safety Controller
appears
Product manual - OmniCore V400XT
173
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
4 Maintenance
4.5.3 Function test of three-position enabling device
Summary of Contents for OmniCore V400XT
Page 1: ...ROBOTICS Product manual OmniCore V400XT...
Page 180: ...This page is intentionally left blank...
Page 338: ...This page is intentionally left blank...
Page 342: ...This page is intentionally left blank...
Page 428: ...This page is intentionally left blank...
Page 460: ...This page is intentionally left blank...
Page 464: ......
Page 465: ......