7.2.1 No LEDs are lit on the controller
Description
No LEDs at all are lit in the controller.
Required test equipment
Equipment needed for troubleshooting:
Note
Equipment
Multimeter
Insulating gloves
Preparations
Action
Make sure that the controller is switched on.
1
Wait 30 s - 1 min to enable start-up sequence.
Check the FlexPendant for errors and warnings.
2
DANGER
Troubleshooting on the controller while powered on must be performed by personnel
trained by ABB or by ABB field engineers.
Recommended working procedure
If no LEDs are lit on the controller during start-up, use this procedure to troubleshoot
what might cause the problem.
Look at the following block diagram to understand how power is connected from
incoming and forward.
Block diagram
AC input
Power inlet
X0
Main switch
Q0
Power unit
A1
X1
X6
L
,N
,P
E
PE
L
,N
L
,N
,P
E
L
,N
Power
supply
T2
X1
X2
2
4
V
T
R
U
N
K
X1
X2
PC
PS
X4
X13
HMI
24V SYS DRV
MS
AC
LED
LED
LED
Main computer
A2
24V PC
LED
X1
24V HMI
LED
HMI
connection
X4
FlexPendant
24V HMI
X9
Robot
signal
exchange
proxy
K2
xx2000000443
Continues on next page
358
Product manual - OmniCore C90XT
3HAC073706-001 Revision: D
© Copyright 2020-2021 ABB. All rights reserved.
7 Troubleshooting
7.2.1 No LEDs are lit on the controller
Summary of Contents for OmniCore C90XT
Page 1: ...ROBOTICS Product manual OmniCore C90XT ...
Page 50: ...This page is intentionally left blank ...
Page 350: ...This page is intentionally left blank ...
Page 354: ...This page is intentionally left blank ...
Page 412: ...This page is intentionally left blank ...
Page 444: ...This page is intentionally left blank ...
Page 448: ......
Page 449: ......