Operation principle
7
Operation principle
What this chapter contains
The chapter describes the operation of the du/dt filter and the intended use.
Operation principle
The drive employs modern IGBT inverter technology. Regardless of frequency, the
drive output comprises pulses of approximately the drive DC bus voltage with a very
short rise time. The pulse voltage can almost double at the motor terminals,
depending on the attenuation and reflection properties of the motor cable and the
terminals. This can cause additional stress on the motor and motor cable insulation.
Modern variable speed drives with their fast rising voltage pulses and high switching
frequencies can generate current pulses that flow through the motor bearings, which
can gradually erode the bearing races and rolling elements.
The common mode filters mainly reduce bearing currents. The du/dt filters also
protect the motor insulation system.
To avoid damage to motor bearings and insulation system:
•
Select and install the cables according to the instructions given in the hardware
manual.
•
Check if the installation needs to be equipped with additional protection
equipment, such as insulated N-end bearings in the motor, or the drive output
filters. The requirements are specified in the drive
Hardware manual
. See chapter
Planning the electrical installation
, section
Selecting the motor,
and chapter
du/dt
filter
.
Summary of Contents for NOCH0070-6 Series
Page 2: ...3AFE58933368 REV G EN EFFECTIVE 2009 09 15 2009 ABB Oy All Rights Reserved ...
Page 6: ...About this manual 6 ...
Page 14: ...Installation 14 Power connection diagrams NOCH0260 60 NOCH0400 60 NOCH0760 60 NOCH0400 60 ...
Page 16: ...Installation 16 NOCH0760 60 ...
Page 17: ...Installation 17 NOCH0400 60 ...
Page 18: ...Installation 18 NOCH0400 60 ...
Page 19: ...Installation 19 AOCH0400 70 AOCH0260 70 ...
Page 27: ...Dimension drawings 27 NOCH0120 60 NOCH0260 60 and NOCH0400 60 du dt kits include 3 filters ...
Page 29: ...Dimension drawings 29 ...