2101510 Rev. AG
Page 6–19
4)
Reducing the number of instantiated applications may be required. Contact
Totalflow technical support for assistance.
6.3.23 RAM File Available Alarm
If the RAM File Available alarm is in warning status, the following procedure will
step the user through the troubleshooting process. On occasion, these instructions
may detour the user to other procedures, and, when complete, they should return
to these procedures to continue.
6.3.23.1
Description
These alarms are indicative of the TFData file resource becoming full. The
recommended files size for TFData is 2 to 3 MB. This alarm may be received after
changing the log period frequency, adding applications or setting up additional
trend files.
6.3.23.2
Instructions
1)
View the alarm history for multiple occurrences. If an occasional warning is
registered, this is not a problem.
2)
View the resources from the PCCU Entry screen to check the available RAM file
space. If applicable, the RAM file space could be increased incrementally.
Please note that when increasing the RAM file space, the
available memory file space is reduced. Caution should be
used.
3)
Following the
instructions in Maintenance, warm start the unit
to defrag the system memory.
4)
Reducing the number of instantiated applications, trend files or lengthening the
log periods may be required. Contact Totalflow technical support for assistance.
6.3.24 FLASH File Available Alarm
If the FLASH File Available alarm is in warning status, the following procedure will
step the user through the troubleshooting process. On occasion, these instructions
may detour the user to other procedures, and, when complete, they should return
to these procedures to continue.
6.3.24.1
Description
These alarms are indicative of a shortage of file space in the 32 MB FLASH.
Typically, this space is not user-accessible; however, instantiating too many
applications may cause an alarm.
6.3.24.2
Instructions
1)
View the alarm history for multiple occurrences. If an occasional warning is
registered, this is not a problem.
2)
Please contact Totalflow technical support for assistance.
6.3.25 Missing Peak - Calibration Not Used
If the Missing Peak-Calibration Not Used is in warning status, the following
procedure will step the user through the troubleshooting process. On occasion,
these instructions may detour the user to other procedures, and, when complete,
they should return to these procedures to continue.
6.3.25.1
Description
These alarms are indicative of a missing peak during a calibration cycle and
calibration will not be used.