Figure 9-4: Enable security on terminal board (switch DOWN)
10. On the
Station Setup
tab, click
Re-read
. Verify that the security switch status is
On
). Enforcement of the security codes is in effect.
11. Click
Close
to close PCCU32 connection with device.
Figure 9-5: Security Switch Status: On
IMPORTANT NOTE:
PCCU32 requires the security codes the next time it attempts connection with
the analyzer.
12. Test security code enforcement: Click the
Setup
icon on the PCCU top menu bar.
13. Type the security code in the Level 1-2 Security Code field (
).
14. Click
Close
to exit setup.
15. Click
Entry
.
16. Verify connection is established.