DE FAU LT DATA M AP
DATA MAPPING
50
1TG C908004M0 201
9.2.3. Monitoring with Function Code 03 and 04
Monitoring of the measured (analogue) values from the individual M10x-M is detailed in the
following table.
Modbus
Function
Code
Modbus
Register
Device
Number
Modbus Register
Name
Format
Remarks
3
40001 1
Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3
40002 1
Thermal image
Unsigned Int, 2
Byte
Used thermal
capacity (only
available if TOL
protection func-
tion is used)
3
40003 1
Time
to
trip
Unsigned
Int,
2Byte
Time before
M10x-M will trip
the motor (only
available if TOL
protection func-
tion is used)
3
40004 1
Time to reset
Unsigned Int,
2Byte
Time required be-
fore reset allowed
(only available if
TOL protection
function is used)
3
40005 2
Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3
40006 2
Thermal image Unsigned
Int,
2Byte
Used thermal
capacity
:
:
:
:
:
:
3
40509 128
Phase current L1
%
Unsigned Int,
2Byte
% age L1 Current
3
40510 128
Thermal image Unsigned
Int,
2Byte
Used thermal
capacity
3
40511 128
Time
to
trip
Unsigned
Int,
2Byte
Time before
M10x-M will trip
the motor
3
40512 128
Time to reset
Unsigned Int,
2Byte
Time required be-
fore reset allowed
Table 21 Default Modbus Map Measured Values of M10x-M