Exchange of position sensor

43/68-13 EN

Electrical Linear Actuators for Continuous Modulating Control LME620AI / LME620AN (Contrac) 

19

7

Exchange of position sensor

7.1

Dismounting

- drive actuator into 50% position
- delete the current position settings by pressing the drive buttons 

on the LCP for at least 5

sec.

- switch-off the voltage supply
- disconnect the main plug
- undo the four fastening screws (1) of the pin strip carrier and push the carrier aside
- undo the two fastening screws (2) of the position sensor, pull the sensor out of the gears 
- disconnect the plug of the signal cable on the sensor pcb

7.2

Mounting

The toothed gear pair of the position sensor is held in place by a tension spring (3), to ensure a back-
lash-free contact when the direction of rotation is reversed

- set the stop pin to the center position, as seen in figure 23
- align the sensor and its gears with the actuator; set the first toothed gear in approx. 12:00 o’clock

position (see fig. 24) onto the drive shaft gear (4) 

- slightly move the sensor back and forth to pre-tension the toothed gears until the second toothed

gear snaps in

- fasten the screws (2) tightly.

Finally provide a new basic setting of the actuator operating range. See the Set Up chapter in the ac-
tuator and / or electronic unit manual for details. 

Fig. 23: Position sensor

Fig. 24: Mounting position

and 

(d0181rxa)

3

(68d_0048)

2

1

Summary of Contents for LME620-AI

Page 1: ...P R O F I B U S PROCESS FIELD BUS Service Instruction 43 68 13 EN Electrical Linear Actuators for Continuous Modulating Control LME620AI LME620AN Contrac Rated Force 4 kN 900 lbf...

Page 2: ...Manufacturer ABB Automation Products GmbH Schillerstr 72 32425 Minden Germany Tel 49 551 905 534 Fax 49 551 905 555 Copyright 2005 by ABB Automation Products GmbH We reserve the right to technical ame...

Page 3: ...trical Connection 11 General 11 Covers 13 Wiring diagrams Integrated electronic unit 13 Wiring diagram 14 Fuses 16 Exchange of position sensor 19 Dismounting 19 Mounting 19 Electrical Test Values 20 T...

Page 4: ...to the freight carrier and your ABB rep resentative Verify that the items on the packing list or bill of lading agree with your own Symbol Signal Word Definitions STOP DANGER DANGER indicates an immin...

Page 5: ...fied personnel When working on the actuator itself or the electronics always observe the locally valid accident pre vention regulations and the regulations concerning the construction of technical ins...

Page 6: ...rated electronics LME620 AN for separate electronics 3 1 LME620 AI Fig 2 LME620AI with dismounted electronic unit 3 2 LME620AN Fig 3 LME620AN with available separate electronic units LME120AI hood wit...

Page 7: ...rques movements temperatures etc and derives the remaining operating time until the next routine maintenance is required Use the configuration program for viewing this information CAUTION All maintena...

Page 8: ...Electrical Linear Actuators for Continuous Modulating Control LME620AI LME620AN Contrac 43 68 13 EN 5 1 Sectional view Fig 4 Sectional view of LME620 motor brake handwheel mechanism thrust rod sensor...

Page 9: ...or position may be changed accidentally by the external load on the drive when the brake is released or the motor is removed remove the rear cover cover with electronics at LME620 AI unscrew the 4 mot...

Page 10: ...ring points towards the interior of the gearbox see fig 8 use appropriate squeezer or similar device to press the sealing ring uniformly into the flange see right part of fig 8 5 2 3 Motor installati...

Page 11: ...between the two plates 3 4 press plate 1 down tighten the two grub screws 1 6 Electrical Connection 6 1 General The cable between actuator and electronic unit is connected to the electronic unit via...

Page 12: ...f the actuator does not affect the process 6 1 2 Removal of integrated electronic unit NOTICE If you want to use a faultless running electronic unit for another actuator it is absolutely necessary to...

Page 13: ...manner Continue with the remaining screws Finally tighten the screws in the same order This will ensure a tight seal 6 3 Wiring diagrams Integrated electronic unit 6 3 1 HART The electrical connectio...

Page 14: ...Uv 24V RB 28 29 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 U V W Br Br 1 2 1 2 3 13 14 M 3 H1 H2 PE r00350x1 one side screening ext fuse screen connected at both ends mains sub distribution boar...

Page 15: ...w terminals red green red green Contrac Contrac electronic unit plug plug actuator 24V Uv 30 RB 31 I U 26 27 1 7 2 8 3 9 4 10 13 5 11 14 6 12 15 L N U V W Br Br PE 17 18 19 20 21 22 23 24 17 18 19 20...

Page 16: ...temperature 5 x 20 mm main pcb 2 A slow EAN 823 External fuse external 16 A slow Mains fuse 5 x 20 mm in connection chamber 6 7 A slow 3 15 A slow Analog setpoint input 5 x 20 mm in connection chambe...

Page 17: ...Control LME620AI LME620AN Contrac 17 6 5 1 2 EAN823 Fig 21 Fuses in EAN823 tapholes signal terminals motor terminals terminals for mains fuse fuse for heater fuse for analogue setpoint input cable mai...

Page 18: ...lectrical Linear Actuators for Continuous Modulating Control LME620AI LME620AN Contrac 43 68 13 EN 6 5 1 3 EAS822 Fig 22 Fuses in EAS822 dig output mains fuses fuse fuse f DO1 fuse f DO2 fuse f DO3 De...

Page 19: ...le on the sensor pcb 7 2 Mounting The toothed gear pair of the position sensor is held in place by a tension spring 3 to ensure a back lash free contact when the direction of rotation is reversed set...

Page 20: ...ocess Depending on the actuator version proceed as follows 8 3 1 LME620AI integrated electronic unit remove the plug remove the actuator hood with electronic unit check pins at pin carrier see fig 20...

Page 21: ...eparated electronic unit refer to pin carrier of actuator plug see fig 17 19 Resistance Winding resistance 5 at 20 C motor pin 6 7 7 8 6 8 Winding resistance 5 at 20 C motor pin 1 2 2 3 1 3 3 4 Ohm Wi...

Page 22: ...l panel see also electronic unit instruction both LED flash alternatively actuator failure e g out of adjusted range actuator can not be moved via command buttons or commands from the process control...

Page 23: ...rol panel is ON No No Yes E1 3 internal mains fuse ok E1 4 power supply ON E1 5 voltage level acc to data label R1 3 replace fuse see E1 5 if the fuse blows again R1 4 Hook up the volt age supply chec...

Page 24: ...g acc to wiring diagram see chpt 6 3 No E1 1 Yes No Yes E 2 3 Disconnect actuator and valve Actuator can be moved No Yes E3 4 Motor winding resistance acc to table 3 E 3 5 Check brake Click sound audi...

Page 25: ...10 9 E 3 3 Test mode ac tive D 2 chpt 10 9 Yes Yes No No R 3 1 Set actuator to AUTO mode via confi soft ware If the actuator is still in MAN mode after switching on again change the set tings for Beha...

Page 26: ...easurable and polarity ok No Yes Yes No Yes R4 1 De activate digital input contacts C 4 chpt 10 9 or provide DC 24 V high signal to dig input 1 R4 2 Replace fuse R4 3 Provide setpoint signal and or ch...

Page 27: ...s E4 2 pulses are measurable and po larity ok Yes R5 2 Electronic unit defective R5 1 provide controller signal and check wiring No E6 1 LED signal Failure E 1 1 Yes E6 2 sensor failure E6 3 sensor me...

Page 28: ...d position over run Actuator moves into an end position once it reaches a setpoint de activate close tight in the software settings for modulating control near the end position Actuator position does...

Page 29: ...the subjects in chpt 10 refer to the user interface Use the numbering in table 4 to facilitate the navigation The user interface software does not use any numbering in the menus Table 4 Trouble shooti...

Page 30: ...dify the information contained herein without notice Printed in the Fed Rep of Germany 12 05 ABB 2005 ABB Ltd Salterbeck Trading Estate Workington Cumbria CA14 5DS UK Tel 44 0 1946 830 611 Fax 44 0 19...

Reviews: