1-326
A
<.
550-UH User’s Manual
Technical data
Outside dimensions – R7…R8
Outside dimensions for the R7 and R8 cabinets are defined below.
Additional free space recommendations
In addition to the free space requirements for cooling (
on page
), allow:
•
800 mm (31.5 in) in front of R7/R8 enclosures – room for the cabinet door to
swing open.
•
305 mm (12 in) above R7/R8, IP54 / UL type 12 enclosures – room for fan
replacement.
Outside Dimensions by Frame Size
Enclosure
Ref.
R7
R8
mm
in
mm
in
UL type 1
W
806
31.7
806
31.7
H
2125
83.7
2125
83.7
D
659
25.9
659
25.9
UL type 12
W
806
31.7
806
31.7
H
2318
91.3
2318
91.3
D
659
25.9
659
25.9
BP0017
W
H
D