Embedded fieldbus
The following diagram shows the drives’ integration to the Johnson Controls
Metasys Companion system.
On the N2 Fieldbus each A
YK
550 drive can be accessed by the full complement of
Metasys FMS features, including Change-of-State (COS) monitoring, alarm
notification, scheduling, trend, and totalization.
On one N2 Fieldbus segment there can be up to 32 nodes while integrating A
YK
550
drives with Johnson Controls Metasys.
Drive device type
For the Metasys and Metasys Companion products, the device type for the A
YK
550
drive is VND.
N2 analog input objects
The following table lists the N2 Analog Input objects defined for the A
YK
550 drive.
N2 Analog Inputs:
Number
Object
Drive
Parameter
Scale
Factor
Units
Range
AI1
OUTPUT FREQUENCY
0103
10
Hz
0…250
AI2
RATED SPEED
Note 1
10
%
0 …100
AI3
SPEED
0102
1
rpm
0 …9999
AI4
CURRENT
0104
10
A
0…9999
AI5
TORQUE
0105
10
%
-200…200
AI6
POWER
0106
10
kW
0…9999
AI7
DRIVE TEMPERATURE
0110
10
°
C
0 …125
AI8
KILOWATT HOURS
0115
1
kWh
0…65535
PC-Version
Converter
Panel Version/LTD
N2 Fieldbus
PC Version
Panel Version/LTD
RS232 -RS485 Converter
Summary of Contents for Johnson Controls AYK550-UH
Page 2: ......
Page 8: ...1 8 A 550 UH User s Manual Table of contents ...
Page 32: ...1 32 A 550 UH User s Manual Installation ...
Page 66: ...1 66 A 550 UH User s Manual Application macros ...
Page 186: ...1 186 A 550 UH User s Manual Parameters ...
Page 333: ...A 550 UH User s Manual 1 333 Technical data ...