5.3 Configuring the IRC5 controller
Description
This configuration example uses the PROFINET configuration file,
ippnio.xml
,
created in section
Creating the PROFINET configuration file on page 42
. It shows
how to use the PROFINET configuration file and how to add the configuration
definitions to the system parameters.
Internal controller configuration
Use this procedure to configure the PROFINET controller in the IRC5 controller,
using the
Configuration Editor
in RobotStudio.
Note
Action
Start RobotStudio and connect to the IRC5
controller. Request write access.
1
Use the
File Transfer
tool in RobotStudio,
or an external FTP client.
Download the
ippnio.xml
configuration file
to the
HOME
directory of the currently used
RobotWare system.
2
Click
Configuration Editor
and select
I/O
System
.
3
For more information about the parameters,
see
.
In the type list, click
Industrial Network
and then right-click in the workspace on
the PROFINET item and select
Edit Indus-
trial Network
.
4
xx1500000937
Enter the parameter values for the industri-
al network.
•
Connection
, select the used Ether-
net connector.
Note
The Connection value is configured
in
Communication
topic. A default
connection is created for
PROFINET. For information about
IP address configuration, see
Tech-
nical reference manual - System
parameters
, section 2.2 Communic-
ation, Use case 2: isolated LAN 3.
•
Configuration File
, the path to the
ippnio.xml
file.
•
PROFINET Station name
, the ro-
bot's PROFINET name id on the
PROFINET network.
Click
OK
.
5
Restart the IRC5 controller.
6
In this example, the et200_test device
(found in the example file ippnio.xml) is
added.
If needed, change the signal names on the
added I/O device.
7
Restart the IRC5 controller to connect to
the configured I/O device.
8
Application manual - PROFINET Controller/Device
43
3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
5 Configuring the internal controller and external device
5.3 Configuring the IRC5 controller
Summary of Contents for IRC5 Compact
Page 1: ...ROBOTICS Application manual PROFINET Controller Device...
Page 28: ...This page is intentionally left blank...
Page 34: ...This page is intentionally left blank...
Page 40: ...This page is intentionally left blank...
Page 48: ...This page is intentionally left blank...
Page 74: ...This page is intentionally left blank...
Page 78: ...This page is intentionally left blank...
Page 86: ......
Page 87: ......