Limits of Engineering Ranges
THC/RTD Type
C
F
Min.
Max.
Min.
Max.
Type B
–18
1800
0
3270
Type E
–100
900
–140
1650
Power 5/2
Power 3/2
Square Root
Custom Linearizer 1
–999 to +9999
Linear
Custom Linearizer 2
Type J
–100
900
–140
1650
Type K
–100
1300
–140
2350
Type L
–100
900
–140
1650
Type N
–200
1300
–325
2350
Type R&S
–18
1700
0
3090
Type T
–250
300
–400
570
Pt100
–200
600
–325
1100
4
CONFIGURATION…
…4.6.2
Analog Input Configuration
Specify the display range and units of the engineering value
corresponding to the electrical high and low values, within
the limits defined in the following table:
Example
– for an electrical input range of 4.0 to 20.0 mA,
representing a pressure range of 50 to 250 bar, set the 'Low'
value to 50.0 and the 'High' value to 250.0.
Enter the tag name to be displayed on channel indicators and
used to identify the channel in archive files. (8 characters max.).
Note.
Tags with a high percentage of capital letters and
wide characters such as 'W' or 'M' may appear truncated in
some Operator Views. In such cases, use lower case letters
or fewer characters.
Enter the tag name to be displayed in the Process view and used
in the archive files (20 characters max.).
•1 If this parameter is changed, internally recorded data files are recreated and unarchived data is lost.