
When input BLOCK is ON, the function will ignore GI requests and cease all
monitoring activity. Consequently, no transitions will be detected.
The I103POSCMD function is also equipped with two additional commands:
Operate and Cancel. These are hidden in ACT and respond only to base INF +2
and +3 respectively. The base INF (Information Number) parameter is an IEC
60870-5-103 identifier that associates a function in a 103 Master (such as Scada)
with its equivalent in the IED.
4.2.5.2
Function block
GUID-3A31C1F2-1FB5-4DB0-A698-AD3F55738DB1 v1
IEC10000286-1-en.vsd
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286 V1 EN-US
Figure 17:
I103POSCMD function block
4.2.5.3
Signals
PID-6997-INPUTSIGNALS v1
Table 43:
I103POSCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
POSITION
INTEGER
0
Position of controllable object
SELECT
BOOLEAN
0
Select of controllable object
4.2.5.4
Settings
PID-6997-SETTINGS v1
Table 44:
I103POSCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type
InfNo
160 - 236
-
4
160
Information number for command output
4.2.5.5
Supported information types
IED commands with position and select for IEC 60870-5-103,
I103POSCMD
GUID-02A72231-F828-4B19-91A0-8AF3FE681A77 v5
Number of instances: 50
The function type for each function block instance is selected with the parameter
FunctionType
.
The information number must be selected for the command output.
1MRK 511 394-UEN A
Section 4
IEC 60870-5-103 vendor specific implementation
670 series 2.2 IEC
47
Communication protocol manual