ABB i-bus® KNX
PARAMETERS
Example
• Old base setpoint: 21 °C
• Manual adjustment: 1.5 K
• Old temperature setpoint: 22.5 °C
New value is received via group object
• New base setpoint: 18 °C
• New temperature setpoint
– Without manual adjustment reset: 19.5 °C
– With manual adjustment reset: 18 °C
Option
No
Manual adjustment is not reset. The new temperature setpoint is calculated from the value in group
object
Yes
Manual adjustment is reset. The new temperature setpoint corresponds to the value in group object
Prerequisites for visibility
\ Option
Controller channel
\ Parameter
room control unit to physical device input a
\ Option
No
• The parameter is in the parameter window
7.4.154
Reset manual setpoint adjustment when operating mode changes
This parameter is used to define whether manual setpoint adjustment is reset when the operating mode
changes.
Example
• Comfort setpoint: 21 °C
• Manual adjustment: 1.5 K
• Temperature setpoint: 22.5 °C
Change in operating mode (e.g. Economy)
Change the operating mode to comfort
• New temperature setpoint
– Without manual adjustment reset: 22.5 °C
– With manual adjustment reset: 21 °C
Option
No
Manual adjustment is not reset. The new temperature setpoint is calculated from the setpoint set for
the operating mode and the manual adjustment.
Yes
Manual adjustment is reset. The new temperature setpoint corresponds to the setpoint of the active
operating mode (plus any shift via group object
).
Prerequisites for visibility
\ Option
Controller channel
\ Parameter
room control unit to physical device input a
\ Option
No
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
143