ABB i-bus® KNX
PARAMETERS
7.4.140
Temperature input monitoring
This parameter is used to define whether the reception of a temperature value is monitored.
Note
For the monitoring of a physical device input to function, a temperature sensor must be connected
and the corresponding input must be set for the connection of a temperature sensor. The following
settings must be made:
• Parameter
\ Option
Temperature sensor
\ all options except
Via group object
Option
Deactivated
Monitoring is deactivated.
On physical device input x
The reception of a temperature value on the physical device input x (x = a, b, c) is monitored.
The following actions will be performed if no valid temperature is measured at the input for longer
than one minute:
•
Fault Actual temperature (master)
•
Value in the parameter
The following dependent parameters are shown:
•
The following dependent group objects are displayed:
•
Fault Actual temperature (master)
On group object
The following group objects are monitored:
•
•
The set time interval applies to both group objects. If a value is received on one of the group objects,
only the time interval of the affected group object restarts.
If a value is not received on one of the two group objects, the following actions are carried out:
•
Fault Actual temperature (master)
•
Value in the parameter
Control value after exceeding monitoring time
The following dependent parameters are shown:
•
Time interval for cyclical monitoring
•
Control value after exceeding monitoring time
The following dependent group objects are displayed:
•
Fault Actual temperature (master)
Prerequisites for visibility
\ Option
Controller channel
\ Parameter
\ Option
Activated
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
134
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page