ABB i-bus® KNX
PARAMETERS
7.4.134
Monitor receipt of group object "Operating mode normal (master)"
This parameter is used to define whether the monitoring of group object
Note
If no value is received on group object
Operating mode normal (master)
during the set time interval (→
parameter
Time interval for cyclical monitoring
), the following actions are carried out:
• Group object
Error "Operating mode" receipt
is set to "Error"
• Value in the parameter
Operating mode after exceeding monitoring time
becomes valid
Option
Deactivated
Monitoring is deactivated.
Activated
Monitoring is activated.
The following dependent parameters are shown:
•
Time interval for cyclical monitoring
•
Operating mode after exceeding monitoring time
Prerequisites for visibility
\ Option
Controller channel
\ Parameter
\ Option
Activated
• The parameter is in the parameter window
7.4.135
Monitor receipt of group object "Window contact"
This parameter is used to define whether the monitoring of group object
Note
If no value is received on group object
during the set time interval (→
parameter
Time interval for cyclical monitoring
), the following actions are carried out:
• Group object
Error "Window contact" receipt
• Until a new value is received on group object
Building Protection
operating mode
Option
Deactivated
Monitoring is deactivated.
Activated
Monitoring is activated.
The following dependent parameters are shown:
•
Time interval for cyclical monitoring
The following dependent group objects are displayed:
•
Error "Window contact" receipt
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Option
Via group object
\ Parameter
\ Option
Activated
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
131