ABB i-bus® KNX
PARAMETERS
7.4.119
Control value on forced operation
This parameter is used to define the control value set if 1-bit forced operation is activated. The control
value applies only to the active operating mode. The control value is valid until the forced operation is
canceled.
More information: →
.
Option
0 … 100 %
Prerequisites for visibility
\ Parameter
\ Options
Activated 1 bit – 1 active
/
Activated 1 bit – 0 active
• The parameter is in the parameter window
7.4.120
Control value on forced operation active "OFF"
This parameter is used to define the control value if 2-bit forced operation "OFF" is activated. The con-
trol value applies only to the active operating mode. The control value is valid until the forced operation
is canceled.
More information: →
.
Option
0 … 100 %
Prerequisites for visibility
\ Parameter
\ Option
Activated 2 bit
• The parameter is in the parameter window
7.4.121
Control value on forced operation active "ON"
This parameter is used to define the control value set if 2-bit forced operation "ON" is activated. The
control value applies only to the active operating mode. The control value is valid until the forced opera-
tion is canceled.
More information: →
.
Option
0 … 100 %
Prerequisites for visibility
\ Parameter
\ Option
Activated 2 bit
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
123