ABB i-bus
®
KNX
Commissioning
236 2CDC508134D0202 | FCA/S 1.x.x.1
3.3.5.4
Communication objects Heating/Cooling
120
Toggle heating
General
1 bit
DPT 1.100
C, W
If a fan coil operating mode with switching object is selected in the
parameter
Toggle to heating with
will appear. Depending on the selection, the communication object
Toggle heating
decides
whether to use heating or cooling mode.
Telegram value:
0 = Heating
1 = Cooling
121
Valve control values parallel mode
General
1 bit
DPT 1.100
C, W
If a fan coil operating mode with two control values and two valves is selected in
p. 76, the parameter
communication object "Valve control values parallel mode" 1-bit
will appear. If the option
Yes
is selected
for this, both valves can move the same way, e.g. both to 50%. If the communication object is switched off again, the previous
state will be restored.
Telegram value:
0 = No function
1 = Parallel mode