Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 211
3.3.3
Communication objects Valve drive, thermoelectric (PWM) and motor-driven (3-point)
Note
As the functions for all outputs are identical, only the functions of output A and A/B will be described.
No.
Functionality
communication object name
Data type
Flags
10
Control value, heating, ON/OFF
Output A
1 bit
DPT 1.001
C, W
This communication object is enabled if the operating mode
Valve drive, thermoelectric (PWM)
has been selected in
Control value is received as
has been parameterized with
the option
Bit
Output (Valve drive, thermoelectric (PWM))
Telegram value:
0 = OFF
1 = ON
10
Control value, heating,
continuous (PWM)
Output A
1 byte
DPT 5.001
C, W
This communication object is enabled if the operating mode
Valve drive, thermoelectric (PWM)
has been selected in
Control value is received as
has been parameterized with
the option
Byte
Output (Valve drive, thermoelectric (PWM))
The communication object value [0…255] determines the variable mark-to-space ratio of the valve drive. With communication
object value 0 the output switches OFF (valve is closed with normally closed valve drive). With communication object value
255 the output switches ON permanently (valve is fully open with normally open valve drive).
Telegram value:
0 = OFF (valve drive closed)
x = Intermediate values
255 = ON (valve drive opened)
10
Control value, heating,
continuous (3-point)
Output A/B
1 byte
DPT 5.001
C, W
This communication object is enabled if the operating mode
Valve drive, motor-driven (3-point) has been selected in
The communication object value [0…255] determines the control value of the valve drive.
If the communication object value is 0, the output switches OFF (voltage 0 V).
If the communication object value is 255, the output switches ON permanently (full voltage).
Telegram value:
0 = OFF (valve drive closed)
x = Intermediate values
255 = ON (valve drive opened)
10
Control value, heating,
analog (0...10 V)
Output A
1 byte
DPT 5.001
C, W
See communication object 10
Control value, heating, continuous (3-point)