22 9AKK108467A5941 Rev. B | MG/S 11.100.1.1 | EN | Product Manual
Note about navigation in the PDF: Key combination
'Alt + left arrow' jumps to the previous view/page
6.4
Assignment of the physical address
Note
If it is set in ETS that the application is to be downloaded during programming, the download will begin
after assignment of the physical address.
Triggering assignment of the physical address via ETS:
1. Press the
Programming
button.
Programming mode is active.
Programming
LED on.
2. Start programming process in ETS.
Physical address is assigned. Device restarts.
Note
The device performs an ETS reset during assignment of the physical address. All states are reset.
6.5
Software/application
6.5.1
Download reaction
Depending on the PC, it can take up to 90 seconds for the progress bar to appear during a download.
Using an interface that supports "long frames" (e.g. USB/S 1.2 or IPR/S 3.5.1) can significantly shorten the
download time.
6.5.2
Copying, exchanging and converting
This section is not relevant for this device.