ABB i-bus
®
KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 47
3.3.2.2.2
Output A,B: Switch actuator - Time, Flashing parameter window
All settings for the
Time
function –
Staircase lighting, Switching ON/OFF delay
and
flashing
– are
undertaken in this parameter window. It is visible if the
Enable function Time
parameter is enabled in
Output A,B: Switch actuator (only "UP" contact
Observe the contact life span and switching cycles per minute.
Note
For the contact life and switching operations per minute, see Technical data, p 7
Time function
Options:
Staircase lighting
Switching ON/OFF delay
Flashing
This parameter defines the type of
Time
function for each output.
•
Staircase lighting
: The staircase lighting is switched via an ON telegram from the output A
Switch
group object, the value of which can be parametrized. The staircase lighting time starts when the
function is switched on. It is switched off immediately after the staircase lighting time ends.
Note
The
Staircase lighting
function can also be called via the
Switch, Logical connection x
(x = 1, 2) group
object or with a light scene recall.
•
Switching ON/OFF delay
: The output can be switched on or off with a delay via this function.
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......